Page 228 - Sustainability Report 2021 - Indonesia Power
P. 228

Menghadirkan Keberlanjutan
                                  Lingkungan Menuju Karbon Netral




            MENJAGA KEBERLANJUTAN SUMBER DAYA AIR
            MAINTAINING SUSTAINABILITY OF WATER





                      Pengukuran Kualitas Air Limbah Dari Proses Utama Indonesia Power Tahun 2021 [GRI 303-4]
                           Wastewater Quality Measurement from Main Processes of Indonesia Power in 2021 [GRI 303-4]

                                                                 Rata-rata   Nilai
               Titik Penaatan    Parameter      Satuan  Baku Mutu  Korporat  Terendah  Nilai Tertinggi  Ketaatan
              Compliance Point                   Unit            Corporate   Lowest   Highest Value  Compliance
                                                                  Average   Value
             Outlet Waste Water   pH             mg/L     6-9      7,82      6,30       9,00
             Treatment Plant
                           Zat padat tersuspensi (TSS)
                           Total Suspended Solids (TSS)  mg/L  80  15,17     0,30      100,00
                           Besi (Fe) Iron (Fe)   mg/L     10       0,26     0,0029      2,70
                           Phosphat (PO )        mg/L     8        0,54     0,0020      7,92
                                    4
                           Klorin Bebas (Cl )    mg/L     0,50     0,04     0,0010      0,28
                                      2
                           Free Chlorine (Cl )
                                      2
                           Minyak dan Lemak
                           Oil and Grease        mg/L     8        1,97     0,0010      6,90
                           Seng (Zn) Zync (Zn)   mg/L      1       0,05     0,0006      0,71
                           Tembaga (Cu) Copper (Cu)  mg/L  1       0,03     0,0010      0,97
                                                                                                Memenuhi baku
                           Kromium Total (Cr)    mg/L     0,50     0,03     0,0002      0,50    mutu
                           Total Chromium (Cr)                                                  Meeting quality
                           BOD                   mg/L     30       18,75     3,00      30,00    standards
                              5
                           COD                   mg/L     100      61,43     10,00     98,90
                           Total Coliform        mg/L    3.000     130,31    1,80      1.300,00
                           Temperatur Temperature  oC     40       33,72    22,30      39,42
             Outlet Condensor
             (Air Bahang)  Klorin Bebas (Cl )    mg/L     0,50     0,05     0,0010      0,30
                                      2
                           Free Chlorine (Cl )
                                      2
                           pH                     oC      6-9      7,28     6,3200      8,11
             Outlet Basin Cooling
             Tower ke Reinjeksi   Klorin Bebas (Cl )  mg/L  1      0,01     0,0100      0,01
                                      2
             Cooling Tower   Free Chlorine (Cl )
                                      2
             Outlet Basin to the   Zinc          mg/L      1       0,02     0,0080      0,04
             Reinjection
                           Phosphate             mg/L     10       0,19     0,1900      0,20
            *  Baku mutu mengacu pada Peraturan Menteri Negara Lingkungan Hidup Nomor 08 tahun 2009 tentang Baku Mutu Air Limbah Bagi Kegiatan Pembangkit Listrik Tenaga Thermal
            *  Quality standards refer to the State Minister of the Environment Regulation No. 8 of 2009 on the Wastewater Quality Standards for Thermal Power Plant Activities
            Indonesia Power juga telah melakukan pengukuran dan   Indonesia Power measures and calculates wastewater disposal
            perhitungan pembuangan air limbah dengan melakukan   by  monitoring  the  flow  meter,  which  is  recorded  daily  and
            pemantauan  flow  meter yang dicatat harian serta bulanan   monthly, in the Logbook of wastewater disposal from all points of
            dalam  Log book pembuangan air limbah terhadap seluruh   wastewater disposal. In 2021, Indonesia Power's total wastewater
            titik pembuangan air limbah. Selama tahun 2021, total volume   was 3,504,662.09 megaliters, increased by 22.43% compared to
            air limbah Indonesia Power sebanyak 3.504.662,09 megaliter,   2020, which was 2,862,495.46 megaliters. This increase occurred
            meningkat 22,43% dibandingkan tahun  2020 yaitu sebanyak   because there was an increase in operations of SPP Lontar and
            2.862.495,46 megaliter. Peningkatan ini terjadi karena terdapat   CCPP Priok units, in which the electricity generation at the CCPP
            peningkatan  operasional  di  Unit  PLTU  Lontar  dan  PLTGU  Priok,   Priok increased by 84%, thereby increasing the overall volume of
            dimana peningkatan produksi listrik PLTGU Priok mencapai 84%   wastewater in these units. [GRI 303-4]
            sehingga meningkatkan volume secara keseluruhan volume air
            limbah di unit tersebut. [GRI 303-4]












          228                                                              Lapooran Keberlanjutan 2021 PT INDONESIA POWER
   223   224   225   226   227   228   229   230   231   232   233